KP2004TS
KP – TS Series combined intumescent fire and smoke seals.
Features:
- One seal only for fire and all temperatures of smoke.
- Rebated into the door or frame for longevity in service.
- Decorative and protective PVC outer casing.
- Ideal for fire engineered solutions where extra protection is necessary for life safety.
Australia Made
Ensuring the highest standards of production, this product is proudly manufactured in Australia.
Product Features
Seals for this designation are designed to control smoke at ambient temperature conditions.
Fire tests to AS1530/4 have been conducted on one or more proprietary fire door constructions to show that the addition of these seals will not affect the already established fire resistance levels of the fire doors. Strict compliance with AS1905/1 requires each door type to be tested with each item of hardware. For each project, please check with the respective fire door manufacturer to verify that their door construction has the relevant listing for Kilargo Integrity seals.
Hot smoke seals incorporate an intumescent material that rapidly expands in volume upon heating. These types of seals limit the spread of hot smoke and gases produced by fully developed fires.
Designed to contain smoke at 200 degrees C for 30 minutes.
Seals for this designation are designed to conform to the NCC Specification C3.4 for ‘Smoke Doors’
Seals for this designation have been tested in accordance with AS1530/7 for smoke leakage, providing ambient or medium temperature leakage rates across various pressures.
Testing for door assemblies incorporating these seals has been conducted to AS1191 and/or ISO140 Part 3/ISO10140.2.