Wall |
Wall |
WM1 |
Masonry / Concrete |
-/120/- |
IFD44C-LL Cased |
Mounted in casing DD / DG |
1200 x 1200 |
|
|
WM1i |
Masonry / Concrete |
-/120/120 |
IFD44C-LL Cased |
Mounted in casing DD with insulated rating |
250 x 250 or 0.0625m2 |
|
|
WM2 |
Masonry / Concrete |
-/240/- |
IFD44C-LL Cased |
Mounted in casing DD / DG |
300 x 300 |
|
|
WM3i |
Masonry / Concrete |
-/120/120 |
IFD44-LL |
Cell only – Air Transfer with grilles or flat vermin proof mesh |
1200 x 1200 |
|
|
WM4 |
Masonry / Concrete |
-/120/- |
IFD44C-LL Cased |
Mounted hard up to slab with 30mm fire board packer – angles 3 sides only |
300 x 300 |
|
|
WM5 |
Masonry / Concrete |
-/120/120 |
IFDO-LL |
Duct to duct / Duct to grille |
350 DIA |
|
|
WM5i |
Masonry / Concrete |
-/120/120 |
IFDO-LL |
Transfer Air with mesh guard |
350 DIA |
|
|
WM6 |
Masonry / Concrete |
-/120/- |
IFD44C-LL Cased |
Mounted hard up to slab (with no packer) – angles 3 sides only |
300 x 300 |
|
|
WM6i |
Masonry / Concrete |
-/120/120 |
IFD44C-LL Cased |
Mounted hard up to slab (with no packer) – angles 3 sides only |
250 x 250 or 0.0625m2 |
|
|
WD1i |
Dincel |
-/120/120 |
IFD44-LL |
Cell only – Air Transfer with grilles or flat vermin proof mesh |
600 x 600 |
|
|
WD2 |
Dincel |
-/120/- |
IFD44C-LL Cased |
Mounted in casing DD / DG |
600 x 600 |
|
|
WH1 |
Hebel |
-/120/- |
IFD44C-LL Cased |
Mounted in casing DD / DG in 75SS system hebel wall |
300 x 300 |
without build up |
|
WH1i |
Hebel |
-/120/120 |
IFD44C-LL Cased |
Mounted in casing DD with insulation 75SS system hebel wall |
250 x 250 or 0.0625m2 |
|
|
WH2 |
Hebel |
-/120/120 |
IFDO-LL |
DD / DG in 75SS system hebel wall |
350 DIA |
|
|
WH2i |
Hebel |
-/120/120 |
IFD44C-LL Cased |
Mounted in casing DD with insulation 75SS system hebel wall |
250 x 250 or 0.0625m2 |
|
|
WH3i |
Hebel |
-/120/120 |
IFD44-LL |
Cell only – Air Transfers with grilles or flat vermin proof mesh in 75SS hebel wall |
300 x 300 |
without build up |
|
WH4 |
Hebel |
-120/120 |
IFDO-LL |
DD / DG in 75mm hebel wall with FR plasterboard liner on one side |
350 DIA |
|
|
WH4i |
Hebel |
-120/120 |
IFDO-LL |
Transfer Air with mesh guard in 75mm hebel wall with FR plasterboard liner on one side |
350 DIA |
|
|
WH5 |
Hebel |
-/120/- |
IFD44C-LL Cased |
Mounted in casing DD / DG in 75mm hebel wall with plasterboard lining |
300 x 300 |
without build up |
|
WH6i |
Hebel |
-/120/120 |
IFD44-LL |
Cell only – Air Transfer with grilles or flat vermin proof mesh in 75mm hebel wall with plasterboard lining |
300 x 300 |
without build up |
|
WH7 |
Hebel |
-/120/- |
IFD44C-LL Cased |
Mounted in casing tight to underside of slab with 30mm thick packer and angles on 3 side of the IFD on 1 side of the wall |
300 x 300 |
|
|
WH7i |
Hebel |
-/120/120 |
IFD44C-LL Cased |
Mounted in casing DD with insulation rating in 75mm hebel wall with FR plasterboard lining |
250 x 250 or 0.0625m2 |
|
|
WH8i |
Hebel |
-120/120 |
IFD44-LL |
Cell only – Air Transfer with grilles or flat vermin proof mesh in 75SW hebel wall |
300 x 300 |
without build up |
|
WH9 |
Hebel |
-/120/120 |
IFDO-LL |
DD / DG in 75 hebel wall lined with plasterboard |
350 DIA |
|
|
WH9i |
Hebel |
-/120/120 |
IFDO-LL |
Transfer Air with mesh guard in 75mm hebel wall lined with plasterboard |
350 DIA |
|
|
WH10 |
Hebel |
-120/120 |
IFDO-LL |
DD / DG in 75 hebel wall |
350 DIA |
|
|
WH10i |
Hebel |
-120/120 |
IFDO-LL |
Transfer Air with mesh guard in 75mm hebel wall |
350 DIA |
|
|
WH11 |
Hebel |
-/120/- |
IFD44C-LL Cased |
Mounted in casing DD / DG in 75SW system hebel wall |
300 x 300 |
without build up |
|
WP1 |
FR Plasterboard 1 x 16 |
-/90/- |
IFD44C-LL Cased |
Mounted in casing DD / DG |
300 x 300 |
without build up |
|
WP1i |
FR Plasterboard 1 x 16 |
-/90/90 |
IFD44-LL |
Cell only – Air Transfer with grilles or flat vermin proof mesh |
300 x 300 |
without build up |
|
WP2 |
FR Plasterboard 3 x 16 |
-/120/- |
IFD44C-LL Cased |
Mounted in casing DD / DG |
1200 x 1200 |
|
|
WP2i |
FR Plasterboard 3 x 16 |
-/120/120 |
IFD44-LL |
Cell only – Air Transfer with grilles or flat vermin proof mesh |
1200 x 1200 |
|
|
WP3 |
FR Plasterboard 2 x 16 |
-/120/120 |
IFDO-LL |
Duct to duct / Duct to grille |
350 DIA |
|
|
WP3i |
FR Plasterboard 2 x 16 +1 |
-/120/120 |
IFDO-LL |
Transfer Air with mesh guard |
350 DIA |
|
|
WP4 |
FR Plasterboard 25 + 2 |
-/120/120 |
IFDO-LL |
Duct to duct / Duct to grille |
350 DIA |
|
|
WP4i |
FR Plasterboard 25 + 2 + 1 |
-/120/120 |
IFDO-LL |
Transfer Air with mesh guard |
350 DIA |
|
|
WP5 |
FR Plasterboard 3 x 16 + 1 |
-/120/120 |
IFDO-LL |
Duct to duct / Duct to grille |
350 DIA |
|
|
WP5i |
FR Plasterboard 3 x 16 + 1 |
-/120/120 |
IFDO-LL |
Transfer Air with mesh guard |
350 DIA |
|
|
WP6 |
FR Plasterboard 3 x 16 |
-/120/120 |
IFDO-LL |
Duct to duct / Duct to grille |
350 DIA |
|
|
WP7 |
FR Plasterboard 2 x 16 |
-/120/- |
IFD44C-LL Cased |
Mounted in casing DD / DG |
1200 x 1200 |
|
|
WP7i |
FR Plasterboard 2 x 16 |
-/120/120 |
IFD44-LL |
Cell only – Air Transfer with grilles or flat vermin proof mesh |
1200 x 1200 |
|
|
WP8 |
FR Plasterboard 1 x 13 |
-/60/- |
IFD44C-LL Cased |
Mounted in casing DD / DG |
300 x 300 |
without build up |
|
WP8i |
FR Plasterboard 1 x 13 |
-/60/60 |
IFD44-LL |
Cell only – Air Transfer with grilles or flat vermin proof mesh |
300 x 300 |
without build up |
|
WP9 |
FR Plasterboard 2 x 13 |
-/120/- |
IFD44C-LL Cased |
Mounted in casing DD / DG |
1200 x 1200 |
|
|
WP9i |
FR Plasterboard 2 x 13 |
-/120/120 |
IFD44-LL |
Cell only – Air Transfer with grilles or flat vermin proof mesh |
1200 x 1200 |
|
|
WP10 |
Plasterboard 1 x 25 liner + 2 x 13 or 16 layers |
-/120/- |
IFD44C-LL Cased |
Mounted in casing DD / DG |
1200 x 1200 |
|
|
WP12 |
FR Plasterboard 1 x 13 |
-/60/60 |
IFDO-LL |
Duct to duct / Duct to grille |
350 DIA |
|
|
WP12i |
FR Plasterboard 1 x 13 |
-/60/60 |
IFDO-LL |
Transfer Air with mesh guard |
350 DIA |
|
|
WP13 |
FR Plasterboard 1 x 16 |
-/90/90 |
IFDO-LL |
Duct to duct / Duct to grille |
350 DIA |
|
|
WP13i |
FR Plasterboard 1 x 16 |
-/90/90 |
IFDO-LL |
Transfer Air with mesh guard |
350 DIA |
|
|
WP14 |
FR Plasterboard 2 x 13 |
-/120/120 |
IFDO-LL |
Duct to duct / Duct to grille |
350 DIA |
|
|
WP14i |
FR Plasterboard 2 x 13 |
-/120/120 |
IFDO-LL |
Transfer Air with mesh guard |
350 DIA |
|
|
WP15i |
FR Plasterboard 1 x 16 + 1 |
-/90/90 |
IFD44C-LL Cased |
Mounted in casing DD with insulation rating |
250 x 250 or 0.0625m2 |
|
|
WP16i |
FR Plasterboard 2 x 16 + 1 |
-/120/120 |
IFD44C-LL Cased |
Mounted in casing DD with insulation rating |
250 x 250 or 0.0625m2 |
|
|
WP17i |
FR Plasterboard 1 x 13 + 1 |
-/60/60 |
IFD44C-LL Cased |
Mounted in casing DD with insulation rating |
250 x 250 or 0.0625m2 |
|
|
WP18i |
FR Plasterboard 2 x 13 + 1 |
-/120/120 |
IFD44C-LL Cased |
Mounted in casing DD with insulation rating |
250 x 250 or 0.0625m2 |
|
|
WRF1 |
Masonry |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork |
600 x 600 |
|
|
WRF2 |
Hebel |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork |
300 x 300 |
without build up |
|
WRF3 |
Plasterboard 3 x 16 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork |
600 x 600 |
|
|
WRF4 |
Plasterboard 2 x 16 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork |
600 x 600 |
|
|
WRF5 |
Plasterboard 2 x 13 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork |
600 x 600 |
|
|
WRF6 |
Plasterboard 1 x 25 liner + 2 x 13 or 16 layers |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork |
600 x 600 |
|
|
WRF7 |
Plasterboard 1 x 16 |
-/90/- |
IFD44-LL |
Retrofit cell only in ductwork |
300 x 300 |
without build up |
|
WRF8 |
Plasterboard 1 x 13 |
-/60/- |
IFD44-LL |
Retrofit cell only in ductwork |
300 x 300 |
without build up |
|
WRF9 |
Dincel |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork |
600 x 600 |
|
|
WRF1s |
Masonry |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork hard to slab |
300 x 300 |
|
|
WRF2s |
Hebel |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork hard to slab |
300 x 300 |
|
|
WRF3s |
Plasterboard 3 x 16 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork hard to slab |
300 x 300 |
|
|
WRF4s |
Plasterboard 2 x 16 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork hard to slab |
300 x 300 |
|
|
WRF5s |
Plasterboard 2 x 13 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork hard to slab |
300 x 300 |
|
|
WRF6s |
Plasterboard 1 x 25 liner + 2 x 13 or 16 layers |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork hard to slab |
300 x 300 |
|
|
WRF7s |
Plasterboard 1 x 16 |
-/90/- |
IFD44-LL |
Retrofit cell only in ductwork hard to slab |
300 x 300 |
|
|
WRF8s |
Plasterboard 1 x 13 |
-/60/- |
IFD44-LL |
Retrofit cell only in ductwork hard to slab |
300 x 300 |
|
|
WRF9s |
Dincel |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork hard to slab |
300 x 300 |
|
|
WFB1 |
Fire Rated Board |
-/120/- |
IFD44C-LL Cased |
Mounted in casing DD / DG |
300 x 300 |
|
|
WFB1i |
Fire Rated Board |
-/120/120 |
IFD44-LL |
Cell only – Air Transfer with grilles or flat vermin proof mesh |
300 x 300 |
|
|
WFB3 |
Fire Rated Board + 2 x PB |
-/120/- |
IFD44C-LL Cased |
Mounted in casing DD / DG |
300 x 300 |
|
|
WFB3i |
Fire Rated Board + 2 x PB |
-/120/120 |
IFD44-LL |
Cell only – Air Transfer with grilles or flat vermin proof mesh |
300 x 300 |
|
Shaftwall |
Shaftwall |
WSRF1 |
Masonry |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch |
600 x 600 |
|
|
WSRF2 |
Hebel |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch |
600 x 600 |
|
|
WSRF3 |
Plasterboard 3 x 16 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch |
600 x 600 |
|
|
WSRF4 |
Plasterboard 2 x 16 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch |
600 x 600 |
|
|
WSRF5 |
Plasterboard 2 x 13 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch |
600 x 600 |
|
|
WSRF6 |
Plasterboard 1 x 25 liner + 2 x 13 or 16 layers |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch |
600 x 600 |
|
|
WSRF7 |
Plasterboard 1 x 16 |
-/90/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch |
600 x 600 |
|
|
WSRF8 |
Plasterboard 1 x 13 |
-/60/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch |
600 x 600 |
|
|
WSRF9 |
Dincel |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch |
600 x 600 |
|
|
WSRF1s |
Masonry |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch hard to slab |
300 x 300 |
|
|
WSRF2s |
Hebel |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch hard to slab |
300 x 300 |
|
|
WSRF3s |
Plasterboard 3 x 16 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch hard to slab |
300 x 300 |
|
|
WSRF4s |
Plasterboard 2 x 16 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch hard to slab |
300 x 300 |
|
|
WSRF5s |
Plasterboard 2 x 13 |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch hard to slab |
300 x 300 |
|
|
WSRF6s |
Plasterboard 1 x 25 liner + 3 x 13 or 16 layers |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch hard to slab |
300 x 300 |
|
|
WSRF7s |
Plasterboard 1 x 16 |
-/90/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch hard to slab |
300 x 300 |
|
|
WSRF8s |
Plasterboard 1 x 13 |
-/60/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch hard to slab |
300 x 300 |
|
|
WSRF9s |
Dincel |
-/120/- |
IFD44-LL |
Retrofit cell only in ductwork riser branch hard to slab |
300 x 300 |
|
|
WSW1 |
Masonry |
-/120/- |
IFD44C-LL Cased |
Mounted in casing – angle free riser connection |
600 x 600 or 0.36 m2 |
without build up |
|
WSW2 |
Masonry |
-/120/- |
IFD44C-LL Cased |
Mounted in casing – angle free riser connection tight to slab with packer |
300 x 300 |
|
|
WSW3 |
Masonry |
-/120/- |
IFD44C-LL Cased |
Mounted in casing – angle free riser connection tight to slab with IBS rod & mastic |
300 x 300 |
|
|
WSW4 |
Plasterboard 3 x 16 |
-/120/- |
IFD44C-LL Cased |
Mounted in casing – angle free riser connection tight to slab with packer |
300 x 300 |
|
|
WSW5 |
Plasterboard 3 x 16 |
-/120/- |
IFD44C-LL Cased |
Mounted in casing – angle free riser connection tight to slab with IBS rod & mastic |
300 x 300 |
|
|
WSW6 |
Hebel |
-/120/- |
IFD44C-LL Cased |
Mounted in casing – angle free riser connection |
300 x 300 |
without build up |
|
WSW7 |
Hebel |
-/120/- |
IFD44C-LL Cased |
Mounted in casing – angle free riser connection tight to slab with packer |
300 x 300 |
|
|
WSW8 |
Hebel |
-/120/- |
IFD44C-LL Cased |
Mounted in casing – angle free riser connection tight to slab with IBS rod & mastic |
300 x 300 |
|
|
WSW9 |
Plasterboard 3 x 16 |
-/120/- |
IFD44C-LL Cased |
Mounted in casing – angle free riser connection |
600 x 600 or 0.36 m2 |
|
|
WSW10 |
Plasterboard 2 x 16 |
-/120/- |
IFD44C-LL Cased |
Mounted in casing – angle free riser connection |
600 x 600 or 0.36 m2 |
|
|
WSW11 |
Plasterboard 1 x 13 |
-/60/- |
IFD44C-LL Cased |
Mounted in casing – angle free riser connection |
300 x 300 |
without build up |
|
WSW12 |
Plasterboard 2 x 13 |
-/120/- |
IFD44C-LL Cased |
Mounted in casing – angle free riser connection |
600 x 600 or 0.36 m2 |
|
|
WSW13 |
Plasterboard 1 x 16 |
-/90/- |
IFD44C-LL Cased |
Mounted in casing – angle free riser connection |
300 x 300 |
without build up |
|
WSW14 |
Plasterboard 1 x 25 liner + 2 x 13 or 16 layers |
-/120/- |
IFD44C-LL Cased |
Mounted in casing – angle free riser connection |
600 x 600 or 0.36 m2 |
|
|
WSW15 |
Dincel |
-/120/- |
IFD44C-LL Cased |
Mounted in casing – angle free riser connection |
600 x 600 |
|
|
WSW23 |
Masonry |
-/120/- |
IFD44-LL |
Cell only installed in riser with grille on one side |
600 x 600 or 0.36 m2 |
|
|
WSW24 |
Hebel |
-/120/- |
IFD44-LL |
Cell only installed in riser with grille on one side |
300 x 300 |
without build up |
|
WSW25 |
Dincel |
-/120/- |
IFD44-LL |
Cell only installed in riser with grille on one side |
600 x 600 |
|
|
WSW27 |
Plasterboard 1 x 16 |
-/90/- |
IFD44-LL |
Cell only installed in riser with grille on one side |
300 x 300 |
without build up |
|
WSW28 |
Plasterboard 2 x 16 |
-/120/- |
IFD44-LL |
Cell only installed in riser with grille on one side |
600 x 600 or 0.36 m2 |
|
|
WSW29 |
Plasterboard 3 x 16 |
-/120/- |
IFD44-LL |
Cell only installed in riser with grille on one side |
600 x 600 or 0.36 m2 |
|
|
WSW30 |
Plasterboard 1 x 13 |
-/60/- |
IFD44-LL |
Cell only installed in riser with grille on one side |
300 x 300 |
without build up |
|
WSW31 |
Plasterboard 2 x 13 |
-/120/- |
IFD44-LL |
Cell only installed in riser with grille on one side |
600 x 600 or 0.36 m2 |
|
|
WSW32 |
Plasterboard 1 x 25 liner + 2 x 13 or 16 layers |
-/120/- |
IFD44-LL |
Cell only installed in riser with grille on one side |
600 x 600 or 0.36 m2 |
|