KP2004TS

KP – TS Series combined intumescent fire and smoke seals.

 

Features:

  • One seal only for fire and all temperatures of smoke.
  • Rebated into the door or frame for longevity in service.
  • Decorative and protective PVC outer casing.
  • Ideal for fire engineered solutions where extra protection is necessary for life safety.
Features
Download

Australia Made

Ensuring the highest standards of production, this product is proudly manufactured in Australia.

Product Features

Ambient Temperature Smoke

Seals for this designation are designed to control smoke at ambient temperature conditions.

Approved for use on propietary fire doors

Fire tests to AS1530/4 have been conducted on one or more proprietary fire door constructions to show that the addition of these seals will not affect the already established fire resistance levels of the fire doors. Strict compliance with AS1905/1 requires each door type to be tested with each item of hardware. For each project, please check with the respective fire door manufacturer to verify that their door construction has the relevant listing for Kilargo Integrity seals.

Hot Smoke

Hot smoke seals incorporate an intumescent material that rapidly expands in volume upon heating. These types of seals limit the spread of hot smoke and gases produced by fully developed fires.

Medium Temperature Smoke 200C

Designed to contain smoke at 200 degrees C for 30 minutes.

Medium Temperature Smoke C3.4

Seals for this designation are designed to conform to the NCC Specification C3.4 for ‘Smoke Doors’

Proprietary Smoke Doors

Seals for this designation have been tested in accordance with AS1530/7 for smoke leakage, providing ambient or medium temperature leakage rates across various pressures.

Sound Containments

Testing for door assemblies incorporating these seals has been conducted to AS1191 and/or ISO140 Part 3/ISO10140.2.

Product Approvals

Fire tested on proprietary fire door assemblies in accordance
AS1530 Part 4 and AS1905 Part 1
Medium temperature smoke leakage approvals to
AS1530 Part 7
available on proprietary door assemblies
Conforms with NCC Specification
C3.4
smoke sealing requirements
Acoustically tested in accordance with
AS1191, IS140.3 & ISO10140-2
Independent tests have been conducted demonstrating over
100,000
open and close cycles without significant wear.

Product Specifications

Application
Incorporated into the perimeter of fire door assemblies. When exposed to fire conditions, these strip seals expand to many times their original volume, sealing off the door perimeter to prevent the passage of hot smoke & other toxic gases. These seals also incorporate twin sealing fins to provide smoke control across all temperatures. For internal use only. Contact Kilargo for external solutions.
Materials
High performance sodium silicate based intumescent core encapsulated in a rigid flame retardant PVC outer casing with coextruded smoke and acoustic fins. Supplied with aggressive self adhesive backing.
Gap Size
Minimum 2mm – Maximum 3mm. The product sits flush with the edge of the door leaf or door frame edge.
Sizes
Standard lengths: 1000mm, 2100mm, 2400mm, 2700mm, 3000mm. Standard fin height: 4mm
Finish
Standard Colour: Black, Grey
Fixing
The product is fitted into a groove in the door frame or the edge of the door leaf and is fixed using the self-adhesive tape backing.

Download Fact Sheet