Application:
Suitable for fire-engineered designs where this sealing combination is required to be tested in accordance with AS1530 Part 7.
Approvals:
Although tested to AS1530 Part 7 it is important to highlight that the resulting leakage data for this system falls outside the maximum leakage guidelines set out in AS6905.
In fact, all ‘stop-mounted’ door seals will result in greater leakage rates when tested opening towards the heated enclosure (akin to a unit entry door scenario), due to door deflection toward the heat source.
- Please check with our Technical Department for suitability of this sealing system with your proprietary door type.
- Medium temperature leakage data available upon request.
For more information and copies of relevant certificates contact Kilargo