Superseded Intumescent Fire Damper System Selector

Penetration System Building Element FRL Product Application / Mounting Detail Max. Size Condition
Wall
Wall WM1 Masonry / Concrete -/120/- IFD44C-LL Cased Mounted in casing 2400 x 2400
WM3 Masonry / Concrete -/120/- IFD44 Cell only 2400 x 2400 or 5.76 m2
WM3i Masonry / Concrete -/120/120 IFD44 Cell only – Transfer Air with mesh guard 2400 x 1200
WM4 Masonry / Concrete -/120/- IFD44 Cell only – Surface mounted (max peno size 500 x 500) 600 x 600
WM5 Masonry / Concrete -/120/120 IFD44-LL Duct to duct / duct to grill 350 DIA
WM6 Masonry / Concrete -/240/- IFD-O Spiral duct sleeve grouted into penetration (angle free) 150 DIA
WM7 Masonry / Concrete -/120/- IFD-OSS Stainless steel casing 350 DIA
WM8 Masonry / Concrete -/120/- IFD-O Spiral duct sleeve grouted into penetration (angle free) 300 DIA
WM10 Masonry / Concrete -/120/- IFD-O IFD-O Hi-Flow 200 DIA
WM11 Masonry / Concrete -/120/- IFD44 Cell only – various fixing brackets 10m x 600mm
WH1 Hebel -120/- IFD44C-LL Cased Mounted in casing in 75SS system hebel wall 2400 x 2400
WH3 Hebel -120/- IFD44C-LL Cased Mounted in casing in 75SW system hebel wall 2400 x 2400
WH5 Hebel -120/- IFD44C-LL Cased Mounted in casing tight to underside of slab connected to riser but with angles on 3 sides of the IFD on 1 side of the wall 300 x 300
WH6 Hebel -120/- IFD-O Mounted in casing tight to underside of slab 150 DIA
WH7 Hebel -120/- IFD44C-LL Cased Mounted in casing tight to underside of slab with angles on 3 side of the IFD on 1 side of the wall 300 x 300
WH8 Hebel -120/- IFD44 Mounted in casing connected to riser, angle free system 600 x 600 or 0.36 m2
WS1 CSR Security Wall -/90/90 IFD44C-LL Cased DD / DG 600 x 600 with cover grille
WS2 CSR Security Wall -/90/- IFD-O Mounted in casing with angles both sides 300 DIA
WP1 FR Plasterboard 1 x 16 -/90/- IFD44C-LL Cased Mounted in casing with angles both sides 2400 x 2400
WP2 FR Plasterboard 3 x 16 -/120/- IFD44C-LL Cased Mounted in casing with angles both sides 2400 x 2400 or 5.76 m2
WP7 FR Plasterboard 2 x 16 -/120/- IFD44 Cell only with various fixing methods 2400 x 2400 or 5.76 m2
WP8 FR Plasterboard 1 x 13 -/60/- IFD44C-LL Cased Mounted in casing angles both sides 2400 x 2400
WP9 FR Plasterboard 2 x 13 -/90/- IFD44C-LL Cased Mounted in casing angles both sides 2400 x 2400
WP10 FR Plasterboard 1 x 13 -/60/- IFD44 Cell only with various fixing methods 2400 x 2400 or 5.76 m2
WP11 FR Plasterboard 2 x 13 -/90/- IFD44 Cell only with various fixing methods 2400 x 2400 or 5.76 m2
WSP1 Speedpanel -/120/- IFD44C-LL Cased Mounted in casing under slab with fire rated board in top track 1000 x 1000
WSP2 Speedpanel -/120/- IFD44C-LL Cased Mounted in casing above slab with fire rated board in bottom track 1000 x 1000
WSP3 Speedpanel -/120/- IFD44C-LL Cased Mounted in casing 1000 x 1000
WSP4 Speedpanel -/120/- IFD44C-LL Cased Mounted in casing with 2 x layers of 13mm plasterboard 1000 x 1000
WSP5 Speedpanel -/120/- IFD-O Mounted in casing DD / DG 300 DIA
WV1 Vermiculux Board -/120/- IFD44 Cell only – Surface mounted (max peno size 500 x 500) 600 x 600
WV2 Vermiculux Board -/120/- IFD44 Cell only – mounted within wall 800 x 800
WV3 Vermiculux Board + 2 x PB -/120/- IFD44 Cell only – mounted within wall with 2 layers of plasterboard lining 800 x 800
WM5i Masonry / Concrete -/120/120 IFDO-LL Transfer Air with mesh guard 350 DIA
Shaftwall
Shaftwall WSRF1 Masonry / Plasterboard 3 x 16 -/120/- IFD44 Retrofit cell only in ductwork branch in masonry / 3 x 16mm plasterboard shaftwall 600 x 600 or 0.36 m2
WSW1 Masonry / Hebel -/120/- IFD44C-LL Cased Mounted in casing – angle free riser connection 600 x 600 or 0.36 m2
WSW2 Masonry / Hebel -/120/- IFD44C-LL Cased Mounted in casing – angle free riser connection tight to slab with packer 600 x 600 or 0.36 m2
WSW3 Masonry -/120/- IFD-O Mounted in casing – angle free riser connection 300 DIA
WSW4 Plasterboard 3 x 16 -/120/- IFD44C-LL Cased Mounted in casing – angle free riser connection tight to slab with packer 600 x 600 or 0.36 m2
WSW5 Plasterboard 3 x 16 -/120/- IFD44C-LL Cased Mounted in casing – angle free riser connection tight to slab with IBS rod & mastic 600 x 600 or 0.36 m2
WSW6 Plasterboard 3 x 16 -/120/- IFD-O Mounted in casing – angle free riser connection 600 x 600 or 0.36 m2
WSW7 Plasterboard 3 x 16 -/120/- IFD44C-LL Cased Mounted in casing – angle free riser connection 600 x 600 or 0.36 m2
WSW8 Plasterboard 2 x 16 -/120/- IFD44C-LL Cased Mounted in casing – angle free riser connection 600 x 600 or 0.36 m2
WSW9 Plasterboard 2 x 16 -/120/- IFD-O Mounted in casing – angle free riser connection 600 x 600 or 0.36 m2
WSW10 Plasterboard 1 x 13 -/60/- IFD44C-LL Cased Mounted in casing – angle free riser connection 600 x 600 or 0.36 m2
WSW11 Plasterboard 2 x 13 -/90/- IFD44C-LL Cased Mounted in casing – angle free riser connection 600 x 600 or 0.36 m2
WSW12 Plasterboard 1 x 16 -/60/- IFD44C-LL Cased Mounted in casing – angle free riser connection 600 x 600 or 0.36 m2
Floor Slab
Floor Slab FL1 Concrete Slab -/120/- IFD44 No casing in penetration 2400 x 2400 or 5.76 m2
FL2 Concrete Slab -/240/180 IFD44 Mounted in casing 300 x 300
FL3 Concrete Slab -/120/120 IFD44 Mounted in casing 600 x 600 or 0.36 m2
FL5 Concrete Slab -/120/- IFD44 Cell only – surface mounted over or under penetration 600 x 600
FL6 Concrete Slab -/120/120 IFD-O No steel sleeve in penetration 250 DIA
FL7 Concrete Slab -/120/- IFD44 Mounted in steel casing in penetration 2400 x 2400 or 5.76 m2
FLV1 Vermiculux OR Promatect Board -/120/120 IFD44 No casing in penetration 800 x 800
FLV2 Vermiculux OR Promatect Board -/120/120 IFD44 No casing – surface mounted over penetration 800 x 800
FLV3 Vermiculux OR Promatect Board -/120/120 IFD44 No casing – surface mounted under penetration 800 x 800
Ceiling
Ceiling CE1 FR P/Board 2 ply ceiling -/60/60 IFD-CE1 P/Board clad encl. (60min RISF Incipient rated) 600 x 600
CE2 FR P/Board 2 ply ceiling -/60/60 IFD-CE2 P/Board clad encl. open end (60 min RISF Incipient rated) 300 x 300
CE3 FR P/Board 2 ply ceiling -/90/90 IFD-CE3 P/Board panel & IFD (90 min RISF Incipient rated) 150mm diameter
CE4 FR P/Board 2 ply ceiling -/90/90 IFD-CE4 P/Board clad 3 way enclosure (90 min RISF Incipient rated) 440 x 440
Door